BaseRdc(Ohm/kft or Ohm/km) = 0.27327
TcAdj = 1.25025
RdcT_Adj(Ohm/kft or Ohm/km) = 0.341656
RShield = 844.722
Yshield_Circ = 0, Yshield_Eddy = 0.000752098
Function = ComputeSteelArmourPipeLossFactor, Ra = 618.549, Rs = 0
Lambda2 (Armor) = 0.0119057
MF = 1.7, Ycs = 0.000706488, Ycp = 0.000419705, YsShield = 0.000752098, YsSheath = 0, YsShield/Sheath = 0,Ys (Shield + Sheath + Shield/Sheath) = 0.000752098, YsArmor = 0.0119057, Yconduit = 0.0222193
Rac/Rdc(1.03762) = [1 + MF(1.7) * (Ycs(0.000706488) + Ycp(0.000419705) + Yshield(0.000752098) + Ysheath(0)) + Yconduit(0.0222193)] * (1 + Yarmor(0.0119057))
RacT_Adj(Ohm/kft or Ohm/km) = 0.354509
RL'(Ohm/kft or Ohm/km) = 0.354509
Delta(m) = 123.345
Case1: 3 x 1/C unshielded/unsheathed and unarmoured cable with no Main or Aux N or PE wires as per cases 1a & 1b of IEC 60909-2 Table 7 (TT system)
X1 Factor = 1
Unit Conversion Factor = 1